LV surge protection installation

It’s Good to have in mind practical aspects: case of a low voltage  switchboard To achieve the effective installation of the , the surge arrester’s connections to the grid should be as short as possible. Any cable crossed by a impulse current has a significant voltage to be added to the Device (SPD) residual voltage.

nice picture from http://www.lafoudre.com/

nice picture from http://www.lafoudre.com/

Practical example (figure 1):

A copper cable with a length L1 + L2 + L3 = 1 meter crossed by a impulse current = 10 kA during 10 microseconds has roughly 1000V between its two ends. This voltage is added at the SPD protection level and its protective device (eg 1800V) so this is 2800V that “sees” the sensitive electrical equipment

In this case, the sensitive equipment is destroyed because its voltage withstand shocks does not exceed 2500V.

example : figure 1

example : figure 1

The solution consists in reducing the length of the cables like this (Figure 2):

L1 reduction: connect the device close to the electrical power network terminal block

L2 reduction: install the protective device over the surge arrester. The most effective solution is to use a surge arrester with an integrated short circuit protection device (L2 = 0)

L3 reduction: Install an intermediate earthing terminal as close as possible to the SPD earth terminal block, then connect the main earthing protection cable from the ground directly to this intermediate earthing terminal, then connect an other cable between the intermediate earthing terminal and the SPD earth terminal block and finally connect the intermediate earthing terminal to the main earthing terminal.

fig-2

example : figure 2

Didier Mignardot

15 Comments

Leave a Comment