Home › Electrical Engineering Forum › General Discussion › Cable Earth Termination › Re: Cable Earth Termination
2011/02/28 at 4:11 pm
#11859
admin
Keymaster
Hello,
In my opinion, you have to connect the armour to the metal cabinets, at
the two ends of the cable, using EMI cable glands. Then you can earth the
internal shield + tape at only one point. (Preferably at the remote end from
the source of interference).
Bye
BAM