  • #10532
    Abhilash
    Participant

    Dear All,

    Kindly help for my below query,

    We want to type Test our final DIstribution board as per IEC 61439. we are using the MCB/ELCB's schneider make. I want to know what will be the  Rated insulation voltage for the DB: Ui
    =  ??? if  other parameters are as follows

    Rated voltage: Un = 415V

    Rated operational voltage: Ue =  690V      

    Rated impulse withstand
    voltage: Uimp = 
    6kV

    When I checked in the MCB catalogue Ui for MCB is shown as 500V

    If anybody can help me in this matter, I am verymuch thankful.

    #12276
    Spir Georges GHALI
    Participant


    Dear All,

    Kindly help for my below query,

    We want to type Test our final DIstribution board as per IEC 61439. we are using the MCB/ELCB's schneider make. I want to know what will be the  Rated insulation voltage for the DB: Ui
    =  ??? if  other parameters are as follows

    Rated voltage: Un = 415V

    Rated operational voltage: Ue =  690V      

    Rated impulse withstand
    voltage: Uimp = 
    6kV

    When I checked in the MCB catalogue Ui for MCB is shown as 500V

    If anybody can help me in this matter, I am verymuch thankful.


    Dear ;

     

    First, as all MCB are designed and tested accordingly to ” IEC 60898 “, so, the ” Ui = 500V ” because it's defined by ” IEC 60898 “.

     

    About ” MCB's for ” Schneider Electric ” :

         – For all ” MCB : C60…  &  C120… ” the ” Ui = 500 V “.

         – For ” NG125… ” the ” Ui = 690 V “.

     

    About ” ELCB's ” for ” Schneider Electric ” :

         – If you use ” Vigi block ” with ” MCB ” the Ui is equal that for ” MCB “.

         – If you use ” RCCB “, be careful because for some of them ” Ui = 440 V “.

     

    Regards.

     

    said: Abhilash

    #12277
    Abhilash
    Participant

    DEAR SIR,

    In this case we can go for 

    Rated insulation voltage for the DB: Ui …… how much for doing Asta type test with this  DB as per IEC61439.

     

    #12282
    Spir Georges GHALI
    Participant

    Abhilash said:

    DEAR SIR,
     

    In this case we can go for 
     

     

     
     

    Rated insulation voltage for the DB: Ui …… how much for doing Asta type test with this  DB as per IEC61439.
     

     
     

     
     


     

    Dear ;
     

     

    As we use ” Ui ” to do the tests for ” Dielectric , Clearance & Creepage “, and if the DB contains RCCB where for some of them ” Ui : 440V “, in this case we should use ” Ui : 440V ” to do these tests.
     

    But :
     

    – If there's ” MCB ( C60… & C120… )+ Vigi-block ” we can use ” Ui : 500V “.

    – If there's ” MCB ( only NG125… )+ Vigi-block ” we can use ” Ui : 690V “.

     

     
     

     
     

     
     

Viewing 4 posts - 1 through 4 (of 4 total)