load calculation

Viewing 4 posts - 1 through 4 (of 4 total)
  • Author
    Posts
  • #10454
    admin
    Keymaster

    if i want to know, whats load will be need in a apertment in where  3*1.5 ton ac,5*100watts tube light,2*40watts celling fan,1 electric heater 1000watts. i mean how much current need?

    #11970
    erickench
    Participant

    What is the area in square feet? Is it just one apartment or the entire building?

    #11974
    admin
    Keymaster

    kamruzzaman said:

    if i want to know, whats load will be need in a apertment in where  3*1.5 ton ac,5*100watts tube light,2*40watts celling fan,1 electric heater 1000watts. i mean how much current need?


    1. 3*1.5 ton AC cunsumption in current is 16.5Amps when its calculated on 3 phase

    2. 5*500 Watts tube light consumption is 0.69 Amps when its calculated on 3 phase

    3. and all other loads will consume only 1.14 Amps

     

    Total Requirement of current will be 18.4 Amps when its calculated on 3 phase.kamruzzaman said:

    if i want to know, whats load will be need in a apertment in where  3*1.5 ton ac,5*100watts tube light,2*40watts celling fan,1 electric heater 1000watts. i mean how much current need?


    kamruzzaman said:

    if i want to know, whats load will be need in a apertment in where  3*1.5 ton ac,5*100watts tube light,2*40watts celling fan,1 electric heater 1000watts. i mean how much current need?


    #11976
    erickench
    Participant

    18.4 amps can't be correct. You must always assume that the AC and the heater are not going to operate at the same time. You must take the higher of these two loads in your calculations.

Viewing 4 posts - 1 through 4 (of 4 total)