6/8 – Electrical equipment: improve power factor

January 20th, 2010 | Posted in Power quality
Tags: , , ,

How to improve ?

has been defined earlier as a function of active and apparent power. For sinusoidal (undistorted) voltage and current, a vector representation is also possible and helpful.
For most electrical loads like motors, the current I is lagging behind the voltage V by an angle phi.
Ia is called the “active” component of the current.
Ir is called the “reactive” component of the current.

Voltage and current vectors

Voltage and current vectors

The above diagram drawn up for currents also applies to powers, by multiplying each current by the common voltage V.
We thus define:

  • Apparent power:         S = V x l                                          (kVA)
  • Active power:               P = V x la = V x I x cos  phi       (kW)
  • :          Q = V x lr = V x I x sin  phi        (kvar)
Active, reactive and apparent power

Active, reactive and apparent power

The physical unit for the is one volt-ampere-reactive (var), with one kilovolt-ampere-reactive (kvar) often used for commodity.

Thus, the supply source has to provide not only the active power P, but also the Q, resulting in the apparent power S.
It can be easily seen from figure above that for a given active power P, there is a great benefit to decrease the phase angle phi, so that the apparent power and the corresponding current could be reduced.

The principle of “” (or “Reactive Energy Compensation”) is to generate the close to the load, so that the supply source could be relieved. Capacitors are most commonly used to supply reactive energy to inductive loads such as motors.

Qc is the produced by the capacitors. S’ is the apparent power after compensation.

s can be arranged to provide a fixed value of reactive energy or variable values by steps.
For highly fluctuating loads such as lifts, crushers …, electronic compensators have been designed in order to provide fast and continuously varying compensation.

Jacques Schonek

Related posts

11 Comments to “6/8 – Electrical equipment: improve power factor”

  1. farhan says:

    Very amazing and nice post sir, but i have a question that whether we can reduce our electricity bill by power factor correction?

    • Francois says:

      Hello Farhan,
      did you read this other article, i think it will answer to your question :
      5/8 – Electrical equipment: power harmonics, power factor

      regards

    • surya says:

      Dear Farhan,
      when the reactive power is supplied by capacitors the power factor will get improve. this leads to decrease in power consumption too. the power is the rms of reactive and apparent power. so, it causes the reduction in power consumed and the charge you r supposed to pay for the electricity department will get reduced.

      • ocir66 says:

        hello surya…. after looking vector diagram above,, it shows reactive lessen and power factor corrected but the apparent power is still the same… no change..

        energy is equal to kw multiply by hour… these we bill by electric cooperative
        im confuse pls explain.. ty

  2. Shahnawaz says:

    Good post Sir,But what is new ?Capacitor banks are mostly used either in industrial loads and at Power system supply side.
    Dear Farhan we can reduce bills by power factor correction but for commercial loads the power factor is of not so importance.

  3. asdf says:

    Thank you for your great article. I also must say that your layout is a pleasure to view. Keep up the good work

  4. pranay says:

    Power factor is the phase difference between voltage and current.We require capacitor bank because in capacitor current lead voltage and in inductive load voltage lead current in order to compensate that we reqire capacitor bank which will remove ur reactive power and pf will be improved

  5. fj says:

    hi
    dear friend
    you have so good blog
    i invite you to see my website
    tnaks for ur attention
    please write ur comment

  6. sandeep baghel says:

    thanks for this artical

  7. borge79 says:

    gud day! I JUST WANT TO ASK IF THERE IS ANY PROBLEM IN REPLACING FUSES OF POWER FACTOR IF THE CAPACITOR IS NOT DISCHARGE

  8. rohan says:

    nice to read ur article……..may i know the difference between power factor and Q factor..???

Leave a comment

Electrical engineering Community is proudly powered by WordPress
Entries (RSS) and Comments (RSS) and license Creative Commons License

webleads-tracker